Question #: 13889

Question: what does the error code on my vfd mean?

Current Solution

Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

If you have an HY series VFD, the fault codes are below:

OC-1: Over-current during ramp up or over-current at constant speed.
Recommended actions: 1, 2, 3, 4

OC-1: Over-current during ramp up or over-current at constant speed.
Recommended actions: 1, 2, 5, 6

OC-2: Over-current at deceleration or over-current at stop.
Recommended actions: 1, 7, 2, 9, 10

dL: Output short circuit.
Recommended actions: 11, 1, 10

Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
Recommended actions: 12, 13

Fb: Fuse break.
Recommended actions: 14, 10

Lu: Low voltage.
Recommended actions: 15, 16, 17

OH: Over heat of inverter.
Recommended actions: 18, 19, 20

OL-1: Inverter overload 150% per minute
Recommended actions: 2, 21, 22

OL-2: Motor overload 150% per minute.
Recommended actions: 21, 23, 24, 25, 26, 21

dT: Motor over-torque
Recommended actions: 21, 23

E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
Recommended action: 27

bt: Braking transistor damage.
Recommended action: 27

CPu: CPU fault.
Recommended action: 27

E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
Recommended action: 27


List of recommended actions:
If error shows at ramp up or at constant speed:
1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
3. Extend the ramp-up time
4. Decrease the torque and increase the set value.
5. Check if the motor is blocked and if there is a sudden change in load.
6. Check if there is a sudden chance in the power supply voltage.
7. Extend ramp down time
9. DC breaking is too high. Decrease DC breaking
10. Replace the inverter.
11. Check to see if there is a short circuit with the connection wire of the motor.
12. Extend the ramp-down time or add a breaking resistor.
13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
14. Send the inverter for repair.
15. Check whether the input voltage is normal
16. check whether there is a sudden change in load.
17. Check whether there is any phase missing.
18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
19. Check the ambient temperature in the space that the inverter is placed.
20. Check for adequate ventilation for the inverter where it is placed.
21. Check for jamming or any sudden change with respect to mechanical load.
22. Set the V/F curve correctly.
23. The motor is too small.
24. The motor is hot and the insulation of the motor degraded.
25. Check if the voltage has a large variance.
26. Check if there is a phase missing.
27. Contact the supplier

Additional Information:
I have cnc wood carving machine 1325 the inverter showing error 0006

Additional Information:
What is uc3 error

Additional Information:
My inverter read error oc-1 high frequency how you can help me please


Additional Information:
My inverter read error oc-1 high frequency how you can help me please


Additional Information:
203

Additional Information:
E2 error

Additional Information:
Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

Additional Information:


Additional Information:
what does it mean when my spindle VFD shows E o and stops.


Additional Information:
Vfd er.01.5c

Additional Information:
CPFO error displayed reason

Additional Information:
Solve it

Additional Information:
My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
Frequency to Frequency track start. whats wrong with the vactory setting?

Additional Information:
Er20

Additional Information:
Fault 503

Additional Information:
Fault 503

Additional Information:
What VFD do you have?

Additional Information:
When I on the motor the derave right oc2 it move then it stop again

Additional Information:
When I on the motor the derave right oc2 it move then it stop again


Additional Information:
what does it mean when my spindle VFD shows E.Lu.S and stops.

Additional Information:
Dear si my emetron ac drive ERR 05 PROBLEM

Additional Information:
Err04



Additional Information:
Err04


Additional Information:
Error 4

Additional Information:
Error 4

Respond:

Other Possible Solutions to this Question

  • what does it mean when my spindle VFD inverter shows OC-2?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Additional Information:
    When I on the motor the derave right oc2 it move then it stop again

    Additional Information:
    When I on the motor the derave right oc2 it move then it stop again


    Additional Information:
    what does it mean when my spindle VFD shows E.Lu.S and stops.

    Additional Information:
    Dear si my emetron ac drive ERR 05 PROBLEM

    Additional Information:
    Err04



    Additional Information:
    Err04


    Additional Information:
    Error 4

    Additional Information:
    Error 4

    Click the link to add information to this solution:
    what does it mean when my spindle VFD inverter shows OC-2?

  • My VFD has started to dL error at startup, what could be the issue?

    The DL error usually means that there is a short in the wiring going from the VFD to the Spindle. First remove the spindle connection and run the VFD. If "DL" does not appear then this means the short is on the spindle itself. Remember to double check your wiring and to use heat shrink on the soldering points to prevent any shorts or arcing between the points.

    Additional Information:


    Additional Information:
    My drive showing dp when it start


    Additional Information:


    Additional Information:


    Additional Information:


    Additional Information:
    My dovol VFD is telling me do what should I do

    Additional Information:



    Additional Information:



    Additional Information:

    Click the link to add information to this solution:
    My VFD has started to dL error at startup, what could be the issue?

  • I WIRED MY VFD (2.2KW VERSION) AND TRIED TEST RUNNING THE SPINDLE. CONFIGURED TO YOUR SPECS ON THIS WEBSITE, ONLY ISSUE IS WE GOT AN ERROR CODE. ERR 02, DO YOU KNOW WHAT IS? OR HAVE A LIST OF CODES? THANK

    Can you provide the model number of your VFD?

    Yes, I have the "YL600 - 2S - 2K20"

    It just came with a small booklet that is all in Chinese...

    Click the link to add information to this solution:
    I WIRED MY VFD (2.2KW VERSION) AND TRIED TEST RUNNING THE SPINDLE. CONFIGURED TO YOUR SPECS ON THIS WEBSITE, ONLY ISSUE IS WE GOT AN ERROR CODE. ERR 02, DO YOU KNOW WHAT IS? OR HAVE A LIST OF CODES? THANK

  • Can we get a VFD Error Code listing?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Additional Information:
    When I on the motor the derave right oc2 it move then it stop again

    Additional Information:
    When I on the motor the derave right oc2 it move then it stop again


    Additional Information:
    what does it mean when my spindle VFD shows E.Lu.S and stops.

    Additional Information:
    Dear si my emetron ac drive ERR 05 PROBLEM

    Additional Information:
    Err04



    Additional Information:
    Err04


    Additional Information:
    Error 4

    Additional Information:
    Error 4

    Click the link to add information to this solution:
    Can we get a VFD Error Code listing?

  • vfd error code 4 can we get a VFD error code listing?

    Remember, steps to correct and troubleshoot issues with any electrical devices should be done by a professional electrician.

    If you have an HY series VFD, the fault codes are below:

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 3, 4

    OC-1: Over-current during ramp up or over-current at constant speed.
    Recommended actions: 1, 2, 5, 6

    OC-2: Over-current at deceleration or over-current at stop.
    Recommended actions: 1, 7, 2, 9, 10

    dL: Output short circuit.
    Recommended actions: 11, 1, 10

    Ou-1 or 2: Over-voltage at stop, over-voltage at acceleration, over-voltage at constant speed or over-voltage at deceleration
    Recommended actions: 12, 13

    Fb: Fuse break.
    Recommended actions: 14, 10

    Lu: Low voltage.
    Recommended actions: 15, 16, 17

    OH: Over heat of inverter.
    Recommended actions: 18, 19, 20

    OL-1: Inverter overload 150% per minute
    Recommended actions: 2, 21, 22

    OL-2: Motor overload 150% per minute.
    Recommended actions: 21, 23, 24, 25, 26, 21

    dT: Motor over-torque
    Recommended actions: 21, 23

    E.b.S.A or E.b.S.n or E.b.S.d or E.b.S.S: No feedback from the auxiliary coil or the lectromagnetic contactor
    Recommended action: 27

    bt: Braking transistor damage.
    Recommended action: 27

    CPu: CPU fault.
    Recommended action: 27

    E.E.E.S or E.E.E.n or E.E.E.d or E.E.E.A: EEPROM fault
    Recommended action: 27


    List of recommended actions:
    If error shows at ramp up or at constant speed:
    1. Check for a short circuit or partial short circuit and the insulation of the output wire is sufficient.
    2. Increase the capacity or the inverter if it is too small. Replace with an inverter that has a larger capacity
    3. Extend the ramp-up time
    4. Decrease the torque and increase the set value.
    5. Check if the motor is blocked and if there is a sudden change in load.
    6. Check if there is a sudden chance in the power supply voltage.
    7. Extend ramp down time
    9. DC breaking is too high. Decrease DC breaking
    10. Replace the inverter.
    11. Check to see if there is a short circuit with the connection wire of the motor.
    12. Extend the ramp-down time or add a breaking resistor.
    13. Check the mains supply voltage and insure there isn't ant sudden change in voltage.
    14. Send the inverter for repair.
    15. Check whether the input voltage is normal
    16. check whether there is a sudden change in load.
    17. Check whether there is any phase missing.
    18. Check the fan in the inverter. Is it spinning? Is it blocked? Does it have any foreign matter stuck on the fins of the fan? If so, clear the fan.
    19. Check the ambient temperature in the space that the inverter is placed.
    20. Check for adequate ventilation for the inverter where it is placed.
    21. Check for jamming or any sudden change with respect to mechanical load.
    22. Set the V/F curve correctly.
    23. The motor is too small.
    24. The motor is hot and the insulation of the motor degraded.
    25. Check if the voltage has a large variance.
    26. Check if there is a phase missing.
    27. Contact the supplier

    Additional Information:
    I have cnc wood carving machine 1325 the inverter showing error 0006

    Additional Information:
    What is uc3 error

    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    My inverter read error oc-1 high frequency how you can help me please


    Additional Information:
    203

    Additional Information:
    E2 error

    Additional Information:
    Hello , I have an Redsail cnc and I get the following error " UC3 "after that the spindle stops arter a small knocking sound ,would there be an solution to this ?

    Additional Information:


    Additional Information:
    what does it mean when my spindle VFD shows E o and stops.


    Additional Information:
    Vfd er.01.5c

    Additional Information:
    CPFO error displayed reason

    Additional Information:
    Solve it

    Additional Information:
    My Spindle VFD Holip HLPA01D523C get error E.OC.A after factory reset. and now get error E.OC.n after i change the starting mode from Start from Starting
    Frequency to Frequency track start. whats wrong with the vactory setting?

    Additional Information:
    Er20

    Additional Information:
    Fault 503

    Additional Information:
    Fault 503

    Additional Information:
    What VFD do you have?

    Additional Information:
    When I on the motor the derave right oc2 it move then it stop again

    Additional Information:
    When I on the motor the derave right oc2 it move then it stop again


    Additional Information:
    what does it mean when my spindle VFD shows E.Lu.S and stops.

    Additional Information:
    Dear si my emetron ac drive ERR 05 PROBLEM

    Additional Information:
    Err04



    Additional Information:
    Err04


    Additional Information:
    Error 4

    Additional Information:
    Error 4

    Click the link to add information to this solution:
    vfd error code 4 can we get a VFD error code listing?

  • WHAT DOES COPYRIGHT MEAN

    Copyright, a form of intellectual property law, protects original works of authorship including literary, dramatic, musical, and artistic works, such as poetry, novels, movies, songs, computer software, and architecture. Copyright does not protect facts, ideas, systems, or methods of operation, although it may protect the way these things are expressed

    Click the link to add information to this solution:
    WHAT DOES COPYRIGHT MEAN

  • WHAT MOTORS DOES THE BLACK TOOTH USE?
  • WHAT MOTORS DOES THE BLACK TOOTH USE?
  • what is the current draw of the 220v VFD

    The current draw of the 220V VFD is 10 amps. Since the spindle is rated at 2.2kW, and the mains for the US 220V is in the range of 220V to 240V,

    2200W/220V = 10A
    2200W/240V = 9.167A

    So, the rage of current draw will be between 10A and 9A, but it is advisable to provide a buffer of about 5 more amps if possible.

    Click the link to add information to this solution:
    what is the current draw of the 220v VFD

  • WHAT DOES THE GREENBULL KIT INCLUDE AND DO I NEED TO INCLUDE?

    The greenBull 4X comes with all of the components and electronics to assemble the gantry of the machine. You will need to build the table. We provide the rails and roller chain for the X-axis (along the length of the table for full 8 feet of travel). You will need to provide some wire to connect the electronics and a computer to run the machine. You will also need to purchase the software that you will need to run the machine that matches how you will apply the machine. We suggest the mach3 control program. The CAM program is up to you as there are many options out there.

    Click the link to add information to this solution:
    WHAT DOES THE GREENBULL KIT INCLUDE AND DO I NEED TO INCLUDE?

  • What are the physical dimensions of the 2.2kw VFD?

    On Monday, when I get back into the office, I will provide the dimensions for the 2.2kW spindle and I will also provide a drawing of these dimensions on the spindle 2.2kW page. Thanks.

    Additional Information:
    Spindle dimensional specifications:

    - Overall diameter is 80mm
    - The length of the outer housing is 200 mm
    - Diameter of the extension just below the spindle is 36mm and the length is 12mm
    - The Collet shaft diameter is 11.318 and the collet nut diameter is 16.75mm and both extend from the extension approximately 52.5 mm
    - The overall length is 264.5mm not including the air ports and the electrical connector (outer housing 200mm + extension 12mm + collet shaft and nut 52.5 mm).
    - The air ports extend 20 mm from the top of the spindle

    Click the link to add information to this solution:
    What are the physical dimensions of the 2.2kw VFD?

  • WHAT IS THE SHIPPING COST TO MY COUNTRY?

    You can determine if the country is serviceable by:
    - selecting the items you want to purchase on the website
    - go to the cart (shopping cart top left of any webpage)
    - log in, or register
    - Enter the address and click on calculate shipping.

    The webpage will return the direct rates and whether your area is serviced or not. Feel free to enter any address as long as you are able to receive the package from that address.

    The shipping times are determined by the service you select in the shopping cart. If a machine is purchased, we generally have a one week lead time unless otherwise stated in the description of the machine's product page.

    Additional Information:

    Click the link to add information to this solution:
    WHAT IS THE SHIPPING COST TO MY COUNTRY?

  • WHAT IS THE SHIPPING FEE TO MY COUNTRY?

    You can determine if the country is serviceable by:
    - selecting the items you want to purchase on the website
    - go to the cart (shopping cart top left of any webpage)
    - log in, or register
    - Enter the address and click on calculate shipping.

    The webpage will return the direct rates and whether your area is serviced or not. Feel free to enter any address as long as you are able to receive the package from that address.

    The shipping times are determined by the service you select in the shopping cart. If a machine is purchased, we generally have a one week lead time unless otherwise stated in the description of the machine's product page.

    Additional Information:

    Click the link to add information to this solution:
    WHAT IS THE SHIPPING FEE TO MY COUNTRY?

  • what size circuit breaker should I use with the 2.2KW VFD?

    The 2.2kW spindle has a power rating of 2.2kW or 2200 watts.

    If the VFD AC voltage input is rated for 220 volts, then 2200 watts / 220 volts is 10 amps, so a 15 or 20 amp breaker will work.

    If the VFD AC voltage input is rated for 110 volts, then 2200 watts / 110 volts is 20 amps, so a 25 or 30 amp breaker will work.

    Additional Information:



    Additional Information:

    Click the link to add information to this solution:
    what size circuit breaker should I use with the 2.2KW VFD?

  • WHAT IS THE WARRANTY ON COMPLETE UNIT?

    We provide a one year warranty from the date the item is delivered.

    Click the link to add information to this solution:
    WHAT IS THE WARRANTY ON COMPLETE UNIT?

  • MY COMPUTER DOES NOT HAVE A PARALLEL PORT. WHAT DO I NEED?

    If your computer does not have a parallel port, all you will need is a low cost PCI parallel adapter card (these can be found on amazon for $15-$20). If you plan on using a laptop (not recommended) you can try to find a PCMCIA parallel adapter, but many people have frequent issues with this setup. A more expensive solution would be to purchase a USB smooth stepper board. Unfortunately, we do not supply any of these adapters and cannot attest to their reliability.

    Additional Information:
    ur gay

    Additional Information:

    Click the link to add information to this solution:
    MY COMPUTER DOES NOT HAVE A PARALLEL PORT. WHAT DO I NEED?

  • how much does the 2.2kW spindle and the VFD weigh together?

    The weight of the 2.2kW spindle without the VFD (variable frequency drive or inverter) is 11 lbs or 5 kg.

    The 2.2kW spindle with the VFD is 15 lbs or 6.8 kg.

    Additional Information:

    Click the link to add information to this solution:
    how much does the 2.2kW spindle and the VFD weigh together?

  • WHAT IS THE WARRANTY ON YOUR PRODUCTS

    We provide a one year warranty from the date the item is delivered.

    Click the link to add information to this solution:
    WHAT IS THE WARRANTY ON YOUR PRODUCTS

  • DOES THE SPINDLE RUN ON A 50HZ POWER SOURCE?

    The spindle inverter (VFD) will run on a 220V (or between 170V-250V) power source with either 50Hz or 60Hz.

    Click the link to add information to this solution:
    DOES THE SPINDLE RUN ON A 50HZ POWER SOURCE?

Get Help with:
This Product
Orders
Tech Support
Sales
This Product
Order Query
Tech Support
Sales
Not logged in. Log In Register
Track Order(s)
View Order(s)
I Want to Schecule a One-On-One Paid Tech Support Session
Book an Appointment Pertaining to a BuildYourCNC Product (Free)
Ask a Quesion Below (Free):
Book an Appointment Pertaining Other Equipment ($60/half hour)
Book an Immedite Appointment Pertaining Other Equipment ($120/half hour)
Ask a Quesion Below (Free):
Waiting for response... I may not answer immediately, but I was notified on my cellular phone so my response is forthcoming. If I don't respond immediately, you can always go to the [My Account] page to see all of our chats at any time.